Drains and Double Traps

Double traps are no good. That’s the end of this tech tip.

Okay, here’s some detail:

Anytime your drain goes up and down more than once, you have a double trap UNLESS you place an air vent between the two traps that vents ABOVE the drain inlet.

The double trap causes drainage issues because air becomes trapped between the two traps, and air is lighter than water. That causes the air to travel up as the water flows down, resulting in NO DRAINAGE.

A vent allows the air to move instead of becoming trapped. That is why you vent a drain after the first trap if there is another trap or the potential of another trap.

That is also why you vent a drain after the first trap and before a common drain if you connect more than one drain. It helps prevent the possibility of a double trap… and a nasty backup.

In general, just pitch the drain properly, install only one trap, and don’t interconnect (unless required). Do those, and you will have no problem.

That was easy!

—Bryan

Co-Founder and President at Kalos Services, Bryan Orr has been involved in HVAC training for over 15 years. Bryan started HVAC School to be free training HVAC/R across many mediums, For Techs, By Techs.

Contact Bryan by emailing bryan@HVACRSchool.com

Visit https://hvacrschool.com – The place to learn some things you’ve forgotten along the way as well as remind you of some things you forgot to know in the first place.

 

 

FEATURES

EXPLORE MORE

HVACR Train the Trainer

In February, leading manufacturers will unveil their latest innovations at the AHR Expo. A few weeks later, March 22–25, 2026,

Serving HVACR
Professionals