Sizing Return Grilles by Matt Bruner

A few weeks ago, I spent several days redoing a duct system and replacing a furnace for a friend. I had static pressure readings from before the system was replaced, and with the new furnace that I had picked out, I had created a static pressure budget and felt confident I could significantly lower the static pressure on his system.

I was changing out the filter for a 4-inch AprilAire, increasing the size of all the ducts in the attic, and lowering the airflow. One thing I did not take into consideration was the return grille size. When I fired up the unit, adjusted the airflow settings (which are very confusing, thanks Amana!), and began measuring static pressure, a feeling of panic began to build inside of me. I was way above where I thought I would be.

Using my manometer, I quickly realized a large part of my problem was on the return side of the system. How could that be? As HVAC professionals often do, I started messing with stuff to see what was going on. I took the return grille off of the unit, and my static pressure dropped dramatically. At that point, I needed to do some research to size it correctly.

As David Richardson notes in his article on return grille sizing, the best way to go about sizing a return grille is by looking at your target feet per minute (FPM), which is determined by Manual D to keep the noise down. We’ve all heard a return grille whistling or vibrating oddly. Chances are, that return grille was sized too small. The target FPM from Manual D is 400. Then, you look at a manufacturer’s return grille performance sheet and pick a grille that satisfies the FPM and your CFM required. Here’s what that looks like for a stamped face return air grille:

Graph 1

In graph 1, the 5th column to the right is the 400 FPM column, and then you look for your target CFM. My target CFM was 1050. Ideally, I would have put a 30×30 return grille on the unit, but there wasn’t room for that. The best I could do was a 30×12 due to size constraints, which meant my FPM was still too high. What if I had used a commercial return air grille with a better AK (free surface area) factor?

Graph 2

In graph 2, on this chart, the 4th column is the 400 FPM column. The airflow at 400 FPM is 916 CFM for a 30×12 high-end commercial grille vs. 551 CFM for a stamped face grille! The system would have been much quieter and had a lower static pressure if I had understood this and sourced a better grille ahead of time.

If you don’t have access to the performance data for return grilles, you can use this rule of thumb from David’s article:
“An approximate rule of thumb to use when engineering data is not available is to multiply the filter grille area in square inches by 2 CFM for each square inch.  This should keep the face velocity of the filter grille below 400 FPM.  Using this rule of thumb method you would need a 20 X 20 return filter grille for a 2 ton unit rated to move 800 CFM. How often do you see a 20 X 20 return filter grille on a 2 ton unit? Answer: Not often enough.”

David Richardson, “Duct Dynasty: The Importance of Return Air Grilles”

According to this rule of thumb, the return grille I picked at 30×12 would be 360 square inches X two = 720 CFM. In the future, I plan to use this rule of thumb to determine if I need to upsize or change the return grilles. Then I can select some better grilles to lower static pressure and noise for future jobs.

About HVAC School
Co-Founder and President at Kalos Services, Bryan Orr has been involved in HVAC training for over 13 years. Bryan started HVAC School to be free training HVAC/R across many mediums, For Techs, By Techs.

Contact Bryan by emailing bryan@HVACRSchool.com.

Visit https://hvacrschool.com – The place to learn some things you’ve forgotten along the way as well as remind you of some things you forgot to know in the first place.

 

 

 

 

In the Spotlight

FRACCA 2024 0209 Weekly Legislative Update

Provided by Edward Briggs, Vice President of Government Relations and Community Affairs at RSA Consulting Group, the Florida Refrigeration and Air Conditioning Contractors Association (FRACCA) lobbying firm in Tallahassee. HVACR industry-related Excerpts by ACprosite Director Peter Montana. HB 7051 Education by Postsecondary Education & Workforce Subcommittee Education: Revises provisions relating to specified education services; establishes Graduation Alternative to Traditional Education

Read More »

FEATURES

Informing & Supporting
Conditioning Air Professionals
& the Industry